General Features & Benefits Specifications Details


CATV-Absorbed Batteries
    Details:

    Fully Charged Operating Temperature Range:
         -76o (-60oC) to 140oF (60oC)
         140oF (60oC) max. for short duration acceptable

    Float Charging Voltage:
         13.5 to 13.8 VDC @ 68oF (20oC)

    Cycle Service Charging Voltage
         13.8 to 14.1 VDC @ 68oF (20oC)

    Charger Ripple:
         ±30 mv/cell (180mv)

    Terminal:
         Combination flag terminals with .375" clearance
         to accept .312" (8mm) bolt.

    Terminal Hardware Torque:
         75 ins./lbs.

    Check Battery Dimensions



Discharge Performance Watts
Constant Power per Battery @ 77oF (25oC)
(Operating time to End Point Voltage)
End Point Volts Per Cell 5
Min.
10
Min.
15
Min.
20
Min.
30
Min.
40
Min.
50
Min.
1.75 3250 2390 1895 1570 1165 920 757
1.70 3485 2540 2010 1660 1230 973 800
1.67 3600 2595 2040 1680 1235 976 803
1.60 3870 2730 2110 1720 1245 983 808
1.55 3990 2790 2145 1745 1260 988 812



Discharge Performance Amps
Constant Current Amperes @ 77oF (25oC)
(Operating time to End Point Voltage)
End Point Volts Per Cell 60
Min.
3
Hrs.
5
Hrs.
6
Hrs.
8
Hrs.
10
Hrs.
12
Hrs.
20
Hrs.
24
Hrs.
48
Hrs.
72
Hrs.
100
Hrs.
1.90 49.5 20.6 13.5 11.6 9.06 7.48 6.38 4.07 3.46 1.84 1.26 0.92
1.85 54.3 22.4 14.6 12.5 9.80 8.10 6.91 4.41 3.75 2.00 1.38 1.01
1.80 57.4 23.5 15.2 13.0 10.1 8.34 7.10 4.51 3.83 2.04 1.40 1.03
1.75 60.5 24.5 15.8 13.5 10.4 8.58 7.29 4.61 3.91 2.07 1.42 1.04




 