Home
     
 
 

   Cable Services
     · CATV-Gel
     · CATV-Absorbed


 

Site Search











General Features & Benefits Specifications Details


CATV-Gel Batteries
    Details:

    Fully Charged Operating Temperature Range:
         -76o (-60oC) to 140oF (60oC)
         140oF (60oC) max. for short duration acceptable

    Float Charging Voltage:
         13.5 to 13.8 VDC @ 68oF (20oC)

    Cycle Service Charging Voltage
         13.8 to 14.1 VDC @ 68oF (20oC)

    Charger Ripple:
         ±30 mv/cell (180mv)

    Terminal:
         Combination flag terminals with .375" clearance
         to accept .312" (8mm) bolt.

    Terminal Hardware Torque:
         75 ins./lbs.

    Check Battery Dimensions



Discharge Performance Watts
Constant Power per Battery @ 77oF (25oC)
(Operating time to End Point Voltage)
End Point Volts Per Cell 5
Min.
10
Min.
15
Min.
20
Min.
30
Min.
40
Min.
50
Min.
1.75 2840 2100 1675 1400 1050 834 690
1.70 3005 2195 1740 1445 1080 857 708
1.67 3110 2255 1780 1470 1090 864 712
1.60 3355 2390 1865 1530 1120 881 722
1.55 3460 2440 1900 1555 1135 890 728



Discharge Performance Amps
Constant Current Amperes @ 77oF (25oC)
(Operating time to End Point Voltage)
End Point Volts Per Cell 60
Min.
3
Hrs.
5
Hrs.
6
Hrs.
8
Hrs.
10
Hrs.
12
Hrs.
20
Hrs.
24
Hrs.
48
Hrs.
72
Hrs.
100
Hrs.
1.90 46.8 19.5 12.8 11.0 8.57 7.05 6.02 3.84 3.26 1.73 1.18 0.87
1.85 51.2 21.2 13.8 11.9 9.30 7.64 6.52 4.15 3.52 1.87 1.28 0.94
1.80 54.9 22.2 14.4 12.3 9.60 7.87 6.70 4.25 3.61 1.91 1.31 0.96
1.75 58.6 23.1 14.9 12.7 9.90 8.09 6.88 4.35 3.69 1.95 1.34 0.98




 
    Traduzca al espaƱol